THE METER OF CHOICE


The Cadillac® Magnetic Flow Meter has been acknowledged as the industry standard for accuracy and installation flexibility



THE METER OF CHOICE FOR WATER AND WASTEWATER APLLICATIONS

The Cadillac® CMAG magnetic flow meter is a rate and totalizing device, which is capable of measuring liquids of all types and consistency while providing an obstruction free flow path. Due to it's unique flow tube/coil design, it is particularly suitable for new or retrofit Water and Wastewater applications. Employing a unique coil winding pattern and containment/focusing plates the Cadillac magnetic flow meter does not require any flow profiling or piping straight run while still meeting the stated meter accuracy (+/-0.25% of rate). In any conductive liquid application the Cadillac® magnetic flow meter is the number one technology choice due to Cadillac®'s accuracy, linearity, reliability and rangeability.


Like many other volumetric flow meters, the Cadillac® magnetic flow meter is a velocity measuring device which computes flow by multiplying the effective cross sectional area of the flow meter with the detected fluid velocity. The meter has no moving parts and consists of a meter body with encapsulated coils, electrodes and an amplifier assembly. It detects velocity by measuring an induced voltage that is developed by moving the conductive fluid through a magnetic field.


The Water / Wastewater Industry Standard

With the introduction of the magnetic flow meter in the early 1970's it has been a favorite choice for the Wastewater marketplace, due to it's full bore design, no moving parts, and ability to operate in heavy fouling applications. With increased wetted material selections most Water, including potable, applications have also looked to magnetic flow meters as the preferred choice, especially in applications requiring analog (rate) or pulse (totalized) outputs.

APPLICATIONS:


  • Data Source for energy management system, DCS, district-wide systems.

  • Cooling tower Water flow.

  • Potable Water flow.

  • General industrial and domestic Water flow.

  • Industrial and domestic Wastewater flow.

  • Aquifer injection Water flow.

  • Process Water flow.

  • Water based Coolant flow.

  • Water based Slurry flow.

  • Reclamation Water flow.

  • Clarifier Water flow.

FEATURES:


Accuracy

+/-0.25% of the reading for liquids. High accuracy allows significant improvement in both measurement and customer billing.


Rangeability

Typically 300 to 1 turndown or better. With seasonal heating/cooling load variation, the need for a large turndown is essential. Cadillac® magnetic flow meters will accurately measure all load requirements with proper sizing.


Longevity

Mean time between failure (MTBF) of 75 years. With no moving parts and through simple robust design the meter has unmeasured life expectancy.


Modern Electronics

Meeting the challenges of the next millennium. Meters are equipped with electronics capable of registering locally, remotely or interfacing with an energy management system. Built to withstand the toughest conditions.

Flow Profile Independent

The flow meter does not require any flow conditioning or piping straight run as required with other volumetric flow meters. Piping straight run from the centerline of the meter is 1.5 pipe diameters, which is essentially the mating flange face of the piping system

PRINCIPLES OF OPERATION


Faraday’s law states that, when you move a conductor perpendicular through a magnetic field, a voltage will be induced proportional to the velocity of the conductor. A magnetic field is created by a set of coils which are encapsulated and rigidly retained in the meter flow tube and, when a conductive liquid moves through that magnetic field, a pair of electrodes measures the voltage induced by the movement of the liquid. The measurement is independent of conductivity changes in the liquid as long as it remains above the minimum threshold of 3 uS/cm2.

The relationship between the liquid velocity and the induced voltage is expressed in a meter K-factor. The meter K-factor is unique to each and every meter and is documented during a NIST traceable flow test completed prior to shipment. With the K-factor established a highly accurate volumetric flow is calculated by multiplying the cross sectional area of the flow tube by the measured liquid velocity. This volumetric relationship can then be converted to various engineering units and the flow meter converter can then retransmit this information with a 4-20 mA current signal and/or conditioned pulse. An optional integral LCD Indicator/Totalizer is available to locally display and totalize in whatever engineering units preferred.

 FLANGED METER DIMENSIONS




Meter Size 0.5" 1.0" 1.5" 2.0" 3.0" 4.0" 6.0" 8.0" 10.0" 12.0" 14.0" 16.0"
A 5.50" 6.24" 6.75" 7.13" 9.00" 9.50" 10.25" 11.75" 13.75" 15.75" 17.75" 19.75"
B 10.25" 10.75" 11.50" 12.25" 13.50" 15.00" 17.25" 19.50" 21.63" 24.25" 25.88" 28.00"
C 8.50" 8.60" 8.90" 9.25" 9.80" 10.50" 11.70" 12.75" 13.65" 14.70" 15.35" 16.25"
Weight
ANSI Class 150 lb
14 lbs 18 lbs 23 lbs 29 lbs 45 lbs 58 lbs 86 lbs 128 lbs 265 lbs 315 lbs 375 lbs 475 lbs

INSTALLATION


Installation requirements have been redefined with the Cadillac magnetic flow meter. Employing coil and plate shaping techniques the Cadillac® meter provides a uniform magnetic flux distribution within the flow tube, allowing the meter to measure and sample uniformly the entire flow tube area. In addition, the electronics provide high frequency DC square wave signal generation and flow signal sampling, enabling fast response to turbulent or tumbling flow conditions.


In practice, this means the Cadillac® magnetic flow meters do not require piping straight run or flow conditioning, and may be installed next to elbows, tees, valves, etc. without any effect in meter accuracy or stability (see Illustrations below).

In comparison, the straight pipe run requirements for all other magnetic flow meters are as follows:

Downstream of the meter:

Expander (2-5) diameters
Tee - (2-5) diameters
Elbow - (2-5) diameters
Valves - (2-10) diameters

Upstream of the meter:

Expander - (10) diameters
Tees - (5) diameters
Elbow (5) diameters
Valves - (10) diameters
 
(see Illustrations below)


Unlike other technologies such as turbine, variable orifice, pitot tube, orifice plates/DP cells, and Vortex, including the Cadillac® Vortex flow meter, magnetic flow meters do not have a low flow cutoff, essentially allowing the meter to read to zero. With such a wide flow range capability for the technology, most applications can be addressed with meters at full line size.





GENERAL SPECIFICATIONS


  • Meter will consist of a full-bore body with encapsulated and rigidly retained set of coils.

  • Meter available with remote or integral electronics.

  • Meter available with local or remote indication or blind housings.

  • Meter available with pulse and analog (4-20 mA) outputs.

  • Meter will provide instantaneous and totalized flow available at local indicator or remotely through outputs.

  • Meter measures flow using Faraday’s law (Induce voltage is directly proportional to the velocity of the conductive liquid)

  • Meter K-factor is stable and not influenced by external piping or mounting orientation.

  • Meter will have uniform magnetic field flux distribution eliminating piping straight run and flow profiling.

  • Meter will measure fluids with conductivity greater than or equal to 5.0 uS/cm2

  • Meter fluid temperature range:            
    (14°F to 176°F) with integral or remote electronics and EPDM liner.
    (14°F to 248°F) with integral or remote electronics and PFA liner.
    (14°F to 248°F) with integral electronics and Ceramic liner.
    (14°F to 356°F) with remote electronics and Ceramic liner.

  • Meter flow tube operating pressure rating: ANSI 150 or ANSI 300

  • Meter power supply: 100-240 VAC, 50/60 Hz (Optional 24Vdc). Power consumption approximately 17 watts

  • Meter operates with minimum 300 to 1 turndown at stated operating accuracy.

  • Meter will be calibrated to/and be provided with NIST calibration certificate.

  • Meter will have empty pipe detection and contact (DO) available for alarming.

FLOW METER SIZING INFORMATION

The Cadillac® magnetic flow meter has a 304 stainless steel body and is always sold with grounding rings installed. The primary reason for providing grounding rings is to contain the magnetic field within the meter body and to assure the liquid potential is grounded properly. As a consequence, the induced voltage is remarkably free of noise allowing the meter to reliably measure extremely low fluid velocities. The table below lists minimum as well as maximum flow ranges for each meter size, in GPM for liquids and lbs/hr for condensate.

Magmeter Liquid Flow Range Table Condensate Flow Range Table
Nominal Meter
Body Size (inches)
Minimum Volumetric Range (gal/min) Maximum Volumetric
Range (gal/min)
Minimum Condensate
Range (lbs/hr)
Maximum Condensate
Range (lbs/hr)
 0.1" 0.00 - 0.024 0.00 - 0.800 0.00 - 12.00 0.00 - 400.0
 0.17" 0.00 - 0.061 0.00 - 2.020 0.00 - 30.50 0.00 - 1010
 0.25" 0.00 - 0.138 0.00 - 4.585 0.00 - 69.00 0.00 - 2300
 0.5" 0.00 - 0.281 0.00 - 28.00 0.00 - 140.0 0.00 - 14000
 1" 0.00 - 0.782 0.00 - 78.00 0.00 - 391.0 0.00 - 39000
 1.5" 0.00 - 2.000 0.00 - 200.0 0.00 - 1000 0.00 - 100000
 2" 0.00 - 3.122 0.00 - 310.0 0.00 - 1556 0.00 - 155000
 3" 0.00 - 8.000 0.00 - 800.0 0.00 - 4000 0.00 - 400000
 4" 0.00 - 12.50 0.00 - 1250 0.00 - 6250 0.00 - 625000
 6" 0.00 - 28.00 0.00 - 2800 0.00 - 14000 0.00 - 1400000
 8" 0.00 - 50.00 0.00 - 5000 0.00 - 25000 0.00 - 2500000
 10" 0.00 - 78.00 0.00 - 7800 0.00 - 39000 0.00 - 3900000
 12" 0.00 - 112.0 0.00 - 11200 0.00 - 56000 0.00 - 5600000

APPLICATION NOTE

The Cadillac® magnetic flow meter is an excellent choice for gravity flow applications. However for proper flow meter operation the piping and flow tube must be full at all times. This requires the meter to be mounted in such a way to provide a "wet leg" as illustrated below.


PRICE LIST

| Magnetic Flow Meter Model Number Structure | | Magnetic Remote Converters |

| Condensate Meters Price List | | Vortex Meters Price List | | Ultrasonic Meters Price List |

MAGNETIC FLOW METERS
CMAG   Cadillac Magnetic Flow Meter Base
  A   Size 0.5" $1,370.00
  B   Size 1" $1,530.00
  C   Size 1.5" $1,575.00
  D   Size 2 " $1,660.00
  E   Size 3 " $1,735.00
  F   Size 4 " $1,760.00
  G   Size 6 " $2,255.00
  H   Size 8 " $2,580.00
  I   Size 10" $4,310.00
  J   Size 12" $5,475.00
  K   Size 14" $7,485.00
  L   Size 16" $8,850.00
  II   Integral Converter with Indicator/Totalizer $1,770.00
  RC   Remote Converter See Below
  W   Wafer Body (ceramic liner) - Available only through 4" Consult Factory
  F   Flanged Body $0.00
  150   ANSI Class 150 # $0.00
  300   ANSI Class 300 # $325.00
  S   Electrode Material - Stainless Steel $0.00
  X   Electrode Material - Other Consult Factory
  C   Liner Material - PFA (Teflon) Standard 2" and below Consult Factory
  D   Liner Material - EPDM (Rubber) - Available 3" and above $0.00
  S   Ground Ring Material - Stainless Steel $0.00
  X   Ground Ring Material - Other Consult Factory
  FM FM Approvals $0.00



MAGNETIC REMOTE CONVETERS
CMC Cadillac Magmeter Remote Converter Base
R Remote Mounting $1,910.00
I Indicator/Totalizer $275.00
U Universal Mounting Bracket $0.00
XXFT Interconnecting Cable (lengths start @ 30 ft) $5.50/ft
FM FM Approvals $0.00

 

If you have questions, or would like to receive additional information about our products, please contact us



CSSC
EMAG
Data Sheet